Saturday, December 4, 2010

Electrical Actuators

Where a pneumatic supply is not available or desirable it is possible to use an electric actuator to control the valve. Electric actuators use an electric motor with voltage requirements in the following range: 230 Vac, 110 Vac, 24 Vac and 24 Vdc.

There are two types of electrical actuator; VMD (Valve Motor Drive) and Modulating.

VMD (Valve Motor Drive)

This basic version of the electric actuator has three states:
  1. Driving the valve open.
  2. Driving the valve closed.
  3. No movement.
Typical electric valve actuator


 Valve motor drive actuator system

Figure above shows the VMD system where the forward and reverse travel of the actuator is controlled directly from any external 3-position or two 2-position switch units. The switches are rated at the actuator voltage and may be replaced by suitable relays.

Limiting devices are fitted within the VMD actuators to protect the motors from over-travel damage. These devices are based on either the maximum motor torque or physical position limit switches. Both devices stop the motor driving by interrupting the motor power supply.
  • Position limit switches have the advantage that they can be adjusted to limit valve strokes in oversized valves.
  • Torque switches have the advantage of giving a defined closing force on the valve seat, protecting the actuator in the case of valve stem seizure.
  • >If only position limit switches are used, they may be combined with a spring-loaded coupling to ensure tight valve shut-off.
A VMD actuator may be used for on/off actuation or for modulating control. The controller positions the valve by driving the valve open or closed for a certain time, to ensure that it reaches the desired position. Valve position feedback may be used with some controllers.

Modulating
In order to position the control valve in response to the system requirements a modulating actuator can be used. These units may have higher rated motors (typically 1 200 starts/hour) and may have built-in electronics.

A positioning circuit may be included in the modulating actuator, which accepts an analogue control signal (typically 0-10 V or 4-20 mA). The actuator then interprets this control signal, as the valve position between the limit switches.

To achieve this, the actuator has a position sensor (usually a potentiometer), which feeds the actual valve position back to the positioning circuit. In this way the actuator can be positioned along its stroke in proportion to the control signal. A schematic of the modulating actuator is shown in Figure bellow.

 Integral positioning circuit for modulating electric actuators

Pneumatic actuators have an inherent fail-safe feature; should the air supply or control signal fail the valve will close. To provide this function in electric actuators, 'spring reserve' versions are available which will open or close the valve on power or control signal failure. Alternatively, fail-safe can be provided with battery power.

Electric actuators offer specified forces, which may be limited on spring reserve versions. The manufacturer's charts should always be consulted during selection.

When sizing an actuator, it is wise to refer to the manufacturer's technical data sheets for maximum differential pressure across the valve (see Figure bellow).

Another limitation of an electric actuator is the speed of valve movement, which can be as low as 4 seconds / mm, which in rapidly varying systems may be too slow.
Typical manufacturer’s electric actuator selection chart

2 comments:

  1. SUDE - Dampers with Pneumatic and Electrical Actuators, Dampers with Pneumatic and Electrical Actuators India.


    FOR MORE DETAILS
    http://sudeengg.com/product_detail.php?prod_id=182

    ReplyDelete
  2. This blog is very useful and interesting. I like your idea of sharing this post about electrical actuator with us. Thanks for sharing this post.

    Eurotherm Power Controls

    ReplyDelete